2. CONTROL POWER SWITCH/LIGHT (see Figure 3)
A lighted ON/OFF push button switch is used to switch power to the 24 VAC control circuit. The switch
lights up to indicate that the Chiller power is present.
3. BYPASS LIGHT (BLUE)
(see Figure 3)
A blue light is used to indicate when the system is operating at a reduced capacity. The light will cycle on
and off in response to the Temperature Controller when the system temporarily requires less cooling.
4. SAFETY LIGHT (RED
) (see Figure 3)
A red light is used to indicate that a fault has occurred in the Chiller operation. The following conditions will
illuminate the safety light.
A. High refrigerant pressure.
B. Low process water temperature.
C. Low process water flow (optional, see OPTIONAL EQUIPMENT section).
5. HIGHPRESSURE SAFETY
(see Figure 3)
The high-pressure safety will shut down the compressor and pump when the refrigerant head pressure
reaches 240-PSIG for R134A refrigerant units and 350PSIG for R22 refrigerant units. The high pres-
sure switch must be reset manually. The switch is located in the electrical box which must be accessed by
removing the Chiller lid. The high-pressure switch can be re-set by depressing the reset button through the
opening in the electrical box cover. If the control opens again, check the setting with a set of refrigeration
gauges. If the setting is correct, contact the Remcor Technical Service Department.
LOWTEMPERATURE SAFETY
The lowtemperature safety will shut down the compressor and the pump when the process water temper-
ature drops below 35_ F (1.7_ C). The switch will automatically reset when the water temperature is re-
stored to 38_ F (3.3_ C). The low temperature control is located in the electrical box.
START UP
WARNING: Never operate the Chiller with its panels removed.
Always use the power switch to turn off the Chiller when it is not being used (see Fluid
Recommendations page).
Always ensure that all air inlets and outlets are free from obstruction.
Be sure that the reservoir is filled with fluid prior to powering up the unit.
Process Water Flow, Units with Pump and Tank (Standard)
Follow standard plumbing practices and local codes in making water connections. The Chiller inlet and outlet
connections are 3/4. Flexible hose and fittings are recommended for plumbing the system. A No. 20 mesh
strainer should be installed on the Chiller inlet to prevent foreign particles from entering the system and should
be cleaned monthly. Lines should be routed with as few bends as possible. Prevent lines from running near
radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient temperatures should be
insulated to prevent condensation and/or significant liquid heat loss.
After ensuring that the system is free from the obstruction, that all valves are open, and the reservoir when avail-
able is full, push the CONTROL POWER switch to the ON position. The pump should now be operating.
On threephase units such as the CH1502A and the CH1503A, it is important to check the pump rotation.
Remove the leftside panel. Momentarily push the POWER button in and observe the motor shaft. Make sure