CLASSIC 1000
REMOTE COOLER
5.2 WATER COOLED MODEL
Fault finding is very similar to the air cooled model.
Follow the air cooled table on the previous page, with the additions detailed below.
PROBLEM
Product
consistently too
warm.
Product too
warm after a
period of time.
ACTION
Refill with 30% Glycol 70%
water. Check for leaks.
Replace.
Check all the stop valves are
open. Check glycol lines are
not kinked or crushed.
Ensure pump priming
procedure is strictly adhered
to.
Clear blockage. Clean fins as
necessary.
Replace.
Clear blockage. Clear fins as
necessary.
Replace.
POSSIBLE FAULT
No ice bank or water
bath too warm.
Insufficient ice or slow
ice build.
POSSIBLE CAUSE
No coolant in CRU. †
Coolant pump in CRU †
failed.
Coolant not flowing
through Discharge Cooler.
Discharge Cooler airflow
blocked.
Discharge Cooler fan *
failed.
Discharge Cooler airflow
blocked.
Discharge Cooler fan *
failed.
* N.B. The Discharge Cooler fan is controlled by a thermostat mounted
on the liquid line of the refrigeration circuit. The fan may not run
in cold ambients (approximately less than 12°C). On initial start
up (in warm conditions) the fan will not start until the liquid line is
warm.
† N.B. There is a high temperature cut-out mounted on the liquid line of
the refrigeration circuit. If temperatures become excessive, this
thermostat will cut-out the compressor. The device protects the
compressor against loss of coolant flow, loss of 24v supply and loss
of discharge unit airflow.
Both of the above thermostats are auto-reset.